DuctTemperatureBase.UpdateSensorProfileConfig1 Method
Syntax
Java
public static void UpdateSensorProfileConfig1(Sensor sens, int measurementsPerTransmission, double hysteresis, double minimumThreshold, double maximumThreshold, boolean isFahrenheit, Boolean sendSensorUpdate);
Parameters 
Description 
Sensor sens 
the Sensor object to be updated  
int measurementsPerTransmission 
the amount of assessments the sensor where take inbetween heartbeats if during these assesments the value is above or below respective triggering thresholds it will send an aware state message.  
double hysteresis 
A buffer to prevent the sensor from bouncing between standard operation and aware state when the asseessments are very close to a threashold. for example, if a maximum threashold is set to 90 degrees and a hysteresis of 1 degree, then once the sensor takes an assessment of 90.0 degrees and enters the aware state it will remain in the aware state until the temperature readings drop to 89.0 degrees  
double minimumThreshold 
the minimum temperature the sensor can report before it goes aware  
double maximumThreshold 
the maximum temperature the sensor can report before it goes aware  
boolean isFahrenheit 
data is always stored as Celsius so if you are inputting values as Fahrenheit you will want to set this boolean value to true  
Boolean sendSensorUpdate 
a Boolean flag that lets the sensor know if it should send up the new configuration 

 

sets all data for the ProfileConfig1 configuration available on the sensor  

 