ThermostatBase.SensorEdit Method
Syntax
Java
public static void SensorEdit(Sensor sens, Double heartBeat, Double awareStateHeartBeat, Double CoolingThreshold, Double HeatingThreshold, Double CoolingBuffer, Double HeatingBuffer, Double OccupiedCoolingThreshold, Double OccupiedHeatingThreshold, Double OccupiedCoolingBuffer, Double OccupiedHeatingBuffer, Boolean AwareStateTriggers, Integer OccupiedTimeout, Integer FanControl, Integer FanPeriod, Integer FanOnInterval, Integer FanStartTimeForHeater, Integer FanStopTimeForHeater, Integer FanStartDelayForCooler, Integer FanStopDelayForCooler);
Parameters 
Description 
Sensor sens 
sens the Sensor object to be updated  
Double heartBeat 
How often the sensor communicates with the gateway if no activity recorded  
Double awareStateHeartBeat 
How often the sensor communicates with the gateway while in Aware State  
Double CoolingThreshold 
Temperature readings above this value will cause the cooler to turn on  
Double HeatingThreshold 
Temperature readings below this value will cause the heater to turn on  
Double CoolingBuffer 
The cooler will stay on till the temperature reading is this many degrees below the Cooling Threshold  
Double HeatingBuffer 
The heater will stay on till the temperature reading is this many degrees above the Heating Threshold  
Double OccupiedCoolingThreshold 
Temperature readings above this value will cause the cooler to turn on  
Double OccupiedHeatingThreshold 
The heater will stay on till the temperature reading is this many degrees above the Heating Threshold  
Double OccupiedCoolingBuffer 
The cooler will stay on till the temperature reading is this many degrees below the Cooling Threshold  
Double OccupiedHeatingBuffer 
The heater will stay on till the temperature reading is this many degrees above the Heating Threshold  
Boolean AwareStateTriggers 
The selected items will force the sensor to become aware and send a data point to iMonnit  
Integer OccupiedTimeout 
The amount of time after the occupied state has been triggered (button press/motion sense/software button) that the system will revert back to the dual threshold settings  
Integer FanControl 
Various control states for the fan. Auto: HVAC system not the thermostat control the fan. Auto+Periodic: Enable configuration to turn the fan of for a period of time at the beinning of a larger period of time. Meant to be used in conjunction with Fan On Period and Fan Auto Period configuration. If a cooling or heating event occurs, the Perodic Fan event time is reset. Active Fan Control: The thermostat actively controls when the fan turns on/off when the heating/cooling is started and stopped. Meant to be used in conjuction with the various Fan Start Time configurations.(Auto = 0, Auto+Periodic = 1, On = 2, Active Fan Control = 3)  
Integer FanPeriod 
Amount of time the fan is forced on during the Fan Auto Period. Ex: Fan On Period = 10 minutes, Fan Auto Period = 120 minutes. At the beginning of the 120 minute Auto Period the fan will be forced on for 10 minutes. After 10 minutes the fan will turn off. 120 minutes after the fan was forced on the fan will be forced on again. Fan On Period must be less than Fan Auto Period  
Integer FanOnInterval 
Interval in which Fan On Period works. Fan Auto Period must be greater than Fan On Period  
Integer FanStartTimeForHeater 
Fan starts this amount of time after the heater starts  
Integer FanStopTimeForHeater 
Fan stops this amount of time after the heater stops  
Integer FanStartDelayForCooler 
Fan starts this amount of time after the cooler starts  
Integer FanStopDelayForCooler 
Fan stops this amount of time after the cooler starts 

Allows for the update of the specific type of sensor 

 