SootBlowerBase.SensorEdit Method

Allows for the update of the specific type of sensor.

Syntax
C#
public static void SensorEdit(ISensor sens, double? heartBeat, double? activeModeReportInterval, double? activeModeTemperatureDelta, double? activeModePressureDelta, double? activeModeCurrentDelta, int? failedTransmissionsBeforeLinkMode);
Parameters 
Description 
ISensor sens 
sens the Sensor object to be updated  
double? heartBeat 
How often the sensor communicates with the gateway if no activity recorded. 
double? activeModeReportInterval 
How often the sensor sends data in the active mode, from the time of the last reported data. Note: Delta threshold breach may cause data report prior to this interval. 
double? activeModeTemperatureDelta 
While in active measurement mode if the temperature changes by this amount compared to the last reported value the sensor will report immedidately. Note: The sensor enters and stays in active mode when voltage is detected ("Voltage Present"). The sensor  
double? activeModePressureDelta 
While in active measurement mode if the pressure changes by this amount compared to the last reported value the sensor will report immedidately. Note: The sensor enters and stays in active mode when voltage is detected ("Voltage Present"). The sensor leaves active mode when no voltage is detected. 
double? activeModeCurrentDelta 
While in active measurement mode if any of the current readings change by this amount compared to the last reported value the sensor will report immedidately. Note: The sensor enters and stays in active mode when voltage is detected ("Voltage Present"). The sensor leaves active mode when no voltage is detected. 
int? failedTransmissionsBeforeLinkMode 
The number of transmissions the sensor sends without response from a gateway before it goes to battery saving link mode. In link mode the sensor will scan for a new gateway and if not found will enter battery saving sleep mode for 2 hours before trying to scan again. Lower number will allow sensors to find new gateways with fewer missed readings. Higher numbers will cause the sensor to hold it setting in a noisy RF environment better. (Zero will cause the sensor to never enter link mode. to find a new gateway channel the battery will have to be cycled out of the sensor.) 