Name |
Description |
The action control command that will be sent to the sensor is urgent | |
The action control command(s) that will be sent to the sensor | |
Defines in minutes the interval at which the sensor communicates with the gateway when the sensor is in the aware state. Unless triggered to communicate earlier, the sensor will send a data message to the gateway when this many minutes elapse. | |
Identifier of the sensor application type. (Temp/Humidity/etc) | |
Identifier of the sensor application type. (Temp/Humidity/etc) | |
For trigger based sensors (Open/Closed, Water, etc) Determines if the sensor is bistable (triggers both directions) or monostable (triggers one direction) | |
For interval based sensors (Temperature, Humidity, etc) Value used by profiles for calibration | |
For interval based sensors (Temperature, Humidity, etc) Value used by profiles for calibration | |
For interval based sensors (Temperature, Humidity, etc) Value used by profiles for calibration | |
For interval based sensors (Temperature, Humidity, etc) Value used by profiles for calibration | |
For Wi-Fi sensors Determines whether to use short term logging or long term data logging on the sensor when Wi-Fi connection is not available | |
For trigger based sensors (Open/Closed, Water, etc) Sets the event count that must be breached to trigger the event | |
For trigger based sensors (Open/Closed, Water, etc) Sets the time period in ms that the event detection count to increment before it is reset | |
For trigger based sensors (Open/Closed, Water, etc) Determines if the sensor is normally open or normally closed, the other state triggering aware | |
Tracks the version of firmware. Some features are only available on certain firmware versions. | |
If set this flag will cause the General Config 2 page to be sent to the sensor Affected Fields: Recovery, RetryCount | |
If set this flag will cause the General Config 1 page to be sent to the sensor Affected Fields: Report Interval, ActiveStateInterval, TransmitIntervalLink | |
The value of which firmware generation the sensor belongs to ie GEN1, GEN2, WIFI, POEX | |
For interval based sensors (Temperature, Humidity, etc) When leaving aware mode back into standard mode the sensor reading must clear the Max or Min threshold by this amount. | |
For interval based sensors (Temperature, Humidity, etc) If reading is above this value the sensor enters aware mode | |
For interval based sensors (Temperature, Humidity, etc) Sets often between report intervals the sensors samples against thresholds | |
For interval based sensors (Temperature, Humidity, etc) If reading is below this value the sensor enters aware mode | |
Identifier of the sensor application type. (Temp/Humidity/etc) | |
If set this flag will cause the action control command will be sent to the sensor | |
If set this flag will cause the Profile Config 2 page to be sent to the sensor Affected Fields (Interval): Calibration1, Calibration2, Calibration3, Calibration4 | |
If set this flag will cause the Profile Config 1 page to be sent to the sensor Affected Fields (Interval): MeasurementsPerTransmission, MaximumThreshold, MinimumThreshold, Hysteresis Affected Fields (Trigger): EventDetectionCount, EventDetectionPeriod, EventDetectionType, BiStable, RearmTime | |
For trigger based sensors (Open/Closed, Water, etc) sets the amount of time before a bistable trigger is reset to observe another event | |
Defines the number of failed transmission sets before entering link mode | |
Defines in minutes the interval at which the sensor communicates with the gateway. Unless triggered to communicate earlier, the sensor will send a data message to the gateway when this many minutes elapse. | |
Defines the number of back to back attempts in a transmission set | |
Unique numeric identifier of the sensor. | |
Sets the time between link attempts in link mode. Default: 2 |